Smart differential pressure transmitter
ZW3851DR seriesSmart differential pressure transmitterIs the introduction of foreign advanced technology and equipment production of new type of transducer, the key raw materials, components and parts are imported, the whole machine after assembled and tested strictly, this product has the advanced design principle, the variety specification is complete, installation convenient use, etc.Due to the aircraft appearance on the total integration of the current domestic zui is popular, strong commonality and replace ability.For the continuous improvement of the domestic automation level and the development, this series of products in addition to the design cabinet and delicate, more has introduced HART field bus protocol of intelligent function.
Second, the working principle:
ZW3851DR series intelligent differential pressure transmitter is two kinds of medium pressure ventilation with high and low pressure chamber, two functions in the delta components (i.e., sensitive element) on either side of the segregation on the diaphragm, through spacer and components on both sides of the filling liquid to measure the diaphragm.Measuring diaphragm and on both sides of the insulation on the electrodes of a capacitor.When we have different pressure on both sides, to cause measuring diaphragm displacement, the displacement and stress is directly proportional to the difference, so both sides capacitance range, through the link of oscillation and demodulation, is converted into is proportional to the pressure signal.
Applications:
ZW3851DR series intelligent differential pressure transmitter is used for combustion chamber of a stove or furnace micro pressure, primary and secondary air volume and air flow loss detection ideal products.Widely used in petroleum, chemical, electric power, food, paper making, municipal engineering and other industries.
Four, the main features:
1, the super performance measurement for pressure, differential pressure, liquid level, flow measurement;
2, digital precision: + (-) 0.05%;
3, the simulation precision: + + (-) (-) 0.75% 0.1% F.S;
4, the whole performance: + 0.25 F.S (-);
5, stability: 0.25% 6 months;
6, span ratio: 100:1;
7, measuring rate: 0.2 S;
8, miniaturization (2.4 kg) stainless steel flange, easy to install;
9, process connection compatible with other products, the realization of measurement;
10, with H alloy sheath of sensors (technology), and achieved excellent cold and hot stability;
11, 16 computer;
12, standard 4-20 ma, with digital signal based on HART protocol, remote control;
13, support to the field bus and upgrade based on the technology of field control.
Five, the technical parameters:
1, use object: liquid, gas and steam;
2, measuring range: 0-0.25 ~ 1.5 kPa;
3, the output signal: 4 ~ 20 ma DC (special for four wire system);220 v AC power supply, 0 ~ 10 ma DC output;
4, power supply: 12 ~ 45 v DC, general is 24 v DC;
5, load characteristic: related to the power supply, when a power supply voltage on load capacity as shown in figure 3, RL load impedance and voltage Vs relation is: RL 50 or less (v - 12);
6, indicator: pointer linear indication 0 ~ 100% scale and the LCD liquid crystal display;
7, explosion-proof grade: a: flameproof (Exd Ⅱ BT5 or Exd Ⅱ CT6);B: this Ann model (Exia Ⅱ CT6 or Ex ib Ⅱ CT6);
8, range and zero: external continuous adjustable;
9, plus or minus migration: zero after positive transfer and negative transfer, range, measurement range, of the absolute value of the upper limit and lower limit are less than 100% of the measurement range limit.Zui dazheng zui small adjustment range migration quantity of 500%;Zui large amount of negative transfer of zui small adjustment range of 600%;
10, the operating temperature range: - 20 ~ + 88 ℃.
Six, protection function:
1, input overload protection;
2, the output flow limit protection;
3, the output current for a long time short circuit protection;
4, two wire port TVS inhibition transient induction lightning and surge current protection;
5, work power over-voltage protection limit 35 v or less;
6, reverse connect protection work power.
Seven, troubleshooting methods:
If the differential pressure transmitter problems encountered in the use process, we can use the following three methods to solve.
1, test:
1.1, replace detection: will doubt defective parts replacement, judge fault position.Such as: suspected transmitter circuit board failure, can be temporary replacement, to determine the reason.
1.2, division test: will measure circuit split into several parts, such as: power supply, signal output, signal transmitting, signal detection, according to the points of inspection, by Jane to numerous, situated, narrow range, find out the fault location
1.3, open circuit detection: separately from the rest parts of the suspected fault and to see whether the fault disappear, if lost, then determine the malfunction, or step into the next search, such as: smart differential pressure transmitter can't normal Hart, telecommunication, power supply can be disconnected from the table body, the method of field plus a power transmitter power to communicate, to see if the cable stack 2 KHZ electromagnetic signals interfere with communication.
1.4, short circuit detection: in the case of security, the related part of the loop short directly, such as: small difference transmitter output value, guide pressure pipe can be disconnected, from a valve directly to the outside differential pressure signal directly led to the differential pressure transmitter, on both sides to observe the transmitter output, to determine the pipeline wall, leakage of connectivity.
2, questionnaire:
Review before failure of flint, smoke, odor, power supply change, lightning, damp, wrong operation, and maintenance.
3, intuitive method:
Observation circuit of external injury, guide of pressure pipe leaking, overheating in the circuit and power supply switch state, etc.
Differential pressure transmitter is the introduction of foreign advanced technology and equipment in the production of new type of transducer, differential pressure transmitter is usually divided into intelligent differential pressure transmitter, high static pressure differential pressure transmitter and three types of differential pressure transmitter.
Eight, notable matters of installation:
Differential pressure transmitter and throttling device supporting the use of time, met the pressure is low, in the calculation of time often to such a situation, it is calculated the maximum differential pressure is the micro differential pressure, it puts forward high demands on the differential pressure transmitter.
Guide the installation of pressure pipe problem:
1, the differential pressure transmitter because of its small scale, the installation position and different stress caused by uneven pressure changes.(30 degrees slope, will produce 0.2 KPa pressure from left) left.Such a situation, especially in and supporting the use of pig and flowmeter, it is important to note that the installation of the differential pressure transmitter.
2, prevent the transmitter medium in contact with the corrosive or overheating;
3, prevent the dross in the guide tube deposition;
4, guide pressure pipe should be as short as possible;
5, on both sides of fluid column pressure head tube should keep balance;
6, pressure pipe should be installed in the temperature gradient and temperature fluctuation is small, no shock and vibration;
Field measurement, the method of reduce error:
1, guide pressure pipe should be as short as possible;
2, when measuring liquid vapor pressure pipe should be connected up to the flow process piping, its Angle should not be less than 1/12;
3, for gas measurement, pressure pipe should be connected to the flow process piping, down the slope shall be not less than 1/12;
4, liquid guide to avoid high pressure pipe laying, gas guide pipe layout to avoid low;
5, two guide pressure pipe should maintain the same temperature;
6, to avoid friction influence, guide pipe diameter should be large enough;
7, fluid-filled guide should be no gas in the pressure tube;
8, when using a spacer, on both sides of liquid level to the same pipe.
Nine, selection of code:
ZW3851DR | (In the wei and control) | |||||||
code | Scale range KPa | |||||||
2 | 0-0.125~1.5KPa | |||||||
code | The output | |||||||
F | 4-20mA | |||||||
Code name | Structural materials | |||||||
Flange and joint | Vent/drain valve | Isolation diaphragm | Pump the liquid | |||||
22 | 316 stainless steel | 316 stainless steel | 316 stainless steel | Silicone oil | ||||
Code name | Zui big work pressure MPa | |||||||
A- | 1 | |||||||
B- | Special 4 (6.9) | |||||||
code | options | |||||||
M1 | 0-100% linear indicator | |||||||
M2 | LED display table | |||||||
M3 | LCD display table | |||||||
B1 | Bend tubes of stents | |||||||
B2 | Plate bending bracket | |||||||
B3 | Pipe bracket with flat | |||||||
D1 | The upper side discharge valve in the pressure chamber | |||||||
D2 | Lateral release valve at the bottom of the pressure chamber | |||||||
Don't note | 1/2 NPT taper pipe nipple | |||||||
C2 | Jump nipple M20 x 1.5, with the back of the welding Ф 14 pressure tube cone ball connection head | |||||||
d | Flameproof d Ⅱ BT4 | |||||||
i | The Ann type ia Ⅱ CT6 | |||||||
s | Three stainless steel valve group |
Ten, design selection and ordering information:
1, ZW3851DR series micro differential pressure transmitter type according to the selection of specification table according to the need to make sure.
2, selection of specifications in the table Numbers, symbols must be fill in clear, accurate.
3, if you have positive and negative migration, must indicate the migration amount value.
4, differential pressure transmitter to match three valve group, the throttle device, need to be indicated separately.
5, according to the user specified range checking.If the user has no rules, set at maximum range in the transmitter, the check will be carried out under room temperature and atmospheric pressure.
6, need labeling station number, should be indicated when ordering.
7, if the remote transmitter should be used in vacuum and high temperature occasion, special label when you order.
Eight, after-sales service commitment:
1, our company sold by differential pressure transmitter series products appear quality problem, within twelve months for free maintenance.
2, the warranty period, any quality problems such as the products of our company, my company is responsible for free repair or replacement.
3, the warranty period, such as user improper use, damaged products, my company is responsible for the maintenance, charge damage parts cost.
4, after the warranty period appear quality problem, my company is responsible for the maintenance, charge damage parts cost.